D-100 Dual Network Interface Installation Guide 07/14 - 1015 Page 5
1.3 SPECIFICATIONS
RS485 (BACnet MS/TP or MODBUS RTU)
Transceiver: 2-wire, half-duplex
Baud rate: 9600, 19200, 38400 & 76800
Termination: 120 ohms or none (Default: none)
Biasing: None
Flow control: None
BACnet UDP/IP & MODBUS TCP/IP
Transceiver: 10Base T, 10Mbps, Rj45 connection
Default IP address: 192.168.1.24
Default Subnet Mask: 255.255.255.0
BACnet Port: 47808
MODBUS Port: 502
Flow control: None
Address Ranges
MODBUS device address range: 1 – 127 (Default: 017)
BACnet device address range: 1 – 127 (Default: 017)
BACnet Device Instance range: 0 - 4,194,303 (Default: 57017)
SECTION 1: INTRODUCTION
1.1 PURPOSE OF THIS GUIDE
The purpose of this guide is to provide installation and commissioning procedures and basic
operating and servicing instructions for the ONICON D-100 Dual Network Flow Display
Network Interface.
1.2 TYPICAL D-100 NETWORK INTERFACE MODULE
The D-100 is a totalizing display module that provides a local indication of liquid, gas or
steam ow rate and total data. It can also be congured with an optional network interface
to communicate data to the building control network. It is housed in a steel wall mounted
enclosure with a built-in user interface/display.
Steam
Building
Domestic Water Supply
Flow rate and total data to
Data Acquisition System or
Building Control System
120VAC or 24VAC
Input Voltage
BACnet and/or MODBUS
COMMUNICATIONS
TO NETWORK
Local display of
ow data