1.4 PROTOCOL SELECTION
The System-10 Dual Network BTU Meter is provided with an IP connection and a single RS485
connection. Both MODBUS TCP/IP and BACnet UDP/IP are always available from the IP
connection via a single IPv4 IP address. The RS485 connection can be congured for BACnet
MS/TP or MODBUS RTU. The protocol options are selected via dip switch settings. The table
below identies the dip switch settings for each protocol. The switch settings also control
which network is allowed to remotely reset totals on the network.
Dip switch SW3 Protocol selection and reset function settings
Protocols Reset 1 2 3 4
BACnet IP/Modbus TCP/Modbus RTU None Off Off Off Off
BACnet IP/Modbus TCP/Modbus RTU BACnet IP On Off Off Off
BACnet IP/Modbus TCP/Modbus RTU Modbus TCP Off On Off Off
BACnet IP/Modbus TCP/Modbus RTU Modbus RTU On On Off Off
BACnet IP/Modbus TCP/BACnet MSTP None Off Off On Off
BACnet IP/Modbus TCP/BACnet MSTP BACnet IP On Off On Off
BACnet IP/Modbus TCP/BACnet MSTP Modbus TCP Off On On Off
BACnet IP/Modbus TCP/BACnet MSTP BACnet MS/TP On On On Off
Baud Rate Dip
Switches
(See Section 1.6.1)
Protocol Selection
Switches