System-40-BAC BTU Meter Manual 03/15 - 1045-2 Page 22
6.3 DEVICE OBJECT
Property Default Value Read-only or
Writable
Comment
Object Identier 57017 Writable 0-4,194,303
Object Name System-40-XXXXXX Read-only
Object Type Device Read-only
System Status Operational Read-only
Vendor Name ONICON Inc. Read-only
Model Name System-40-BAC Read-only
Firmware Rev. 000.000.000 Read-only
Location Customer Location Writable 32 char. Max
Description Customer Description Writable 32 char. Max
Protocol Version 1 Read-only
Protocol Revision 10 Read-only
Services Supported
Read property, Read property
multiple, Write property, Write
property multiple, Read range,
Who-has, I have, Who-is, I-am,
Device communications control,
Time synchronization, UTC time
synchronization
Read-only
Object Types Supported Analog input, Analog value, Binary
input, Device, Multi-state value,
Trend log multiple
Read-only
Object List (Device, 57017), (analog input, 1 –
10), (analog value, 1 – 22), (binary
value, 1 – 10), (trend log multiple,
1), (multi state value, 1)
Read-only
Max ADPU Length 480 Read-only
Local Time Device current time Read-only
Local Date Device current date Read-only
UTC Offset -300 Writable
Daylight Savings Status False Writable
APDU Timeout 6000 Read-only
# of APDU Retries 3 Writable
Max Master 127 Read-only
Device Address Binding Read-only Active
Database Revision 1 Read-only